GE D20 EME210BASE-T Substation Controllers

GE D20 EME210BASE-T Substation Controllers

Brand: General Electric

Product ID: D20 EME210BASE-T

Condition: New / used

Terms of payment: Paypal、T/T 、Western Union

Category:

Description

GE D20 EME210BASE-T

I. Basic Information


Model: D20 EME (10BASE-T Ethernet Variant) | Part No.:2400-21004Brand: GE General Electric (USA, GE Energy), WESDAC D20/D200 RTU seriesEME = Ethernet & Memory Expansion Main Control Card, with onboard native 10BASE-T RJ45 Ethernet, core CPU communication board for D20 rack-mounted power RTU. The 10BASE-T is fixed physical layer specification of this EME model, designed for substation legacy network reconstruction spare parts.
Mounting: Hot-pluggable slot installation on standard D20 rack via rear backplane bus; Dimension:225(L)×135(W)×30(H)mm, Net Weight≈0.42kg; Military-grade three-proof coated PCB, IP20 cabinet protection, UL & IEC grid certification.Support Software: D20 Config, Toolbox programming software; matched with original factory firmware compatible with full-range D20 I/O modules.Onboard Hardware: Fixed 10BASE-T RJ45 LAN port, RS232+RS485 serial terminals, D20 dedicated backplane parallel bus, RUN/FAULT/COM tri-color LED indicators, fully populated RAM & Flash memory chips.


II. Technical Specification


1. CPU & Memory Configuration

32-bit dedicated power industry processor; Full spec:8MB RAM+16MB Flash, hardware expandable up to 16MB RAM /32MB Flash.Logic scan cycle:2~10ms; Fastest analog telemetry sampling:100ms, support four-remote functions (YT/YX/YK/YTT).Built-in hardware watchdog, memory check, backplane short-circuit self-test; fault triggers communication lockout and front panel alarm.

2. Communication Parameters (Core:10BASE-T Ethernet)

  • Ethernet: Fixed 10BASE-T (10Mbps Half-Duplex, RJ45 twisted pair), protocol stack: Modbus TCP, DNP3.0 TCP, IEC60870-5-104; cannot auto-negotiate to 100M, hardware limited to 10Mbps standard.
  • Serial: RS232/RS485, Modbus RTU, Serial DNP3, IEC60870-5-101 for local protection & instrument connection.
  • D20 Backplane Bus: Max 16pcs DI/DO/AI/AO I/O cards per rack for internal data exchange.

3. Power Supply

DC24V input (18~32VDC wide range), power consumption ≤7W; onboard isolation, surge & Grade3 EMC anti-interference against substation EMI.

4. Environment Spec

Operating: -20℃~+70℃; Storage:-40℃~+85℃; Humidity:5%~95%RH non-condensing; Vibration resistance:5g(5~500Hz).

5. Max I/O Loading Capacity

AI:64ch (4~20mA/0~10V, ±0.1%FS); DI:128ch DC24V dry contact with break detection ≤1ms response;DO:64ch relay output (5A@250VAC); Pulse input:32ch, max 1kHz for energy metering pulse.



III. Key Features


  1. Fixed 10Mbps 10BASE-T Ethernet: Early-generation EME hardware fixed 10BASE-T, applicable for legacy industrial 10M star network of old substations, no 100M auto-switch function.
  2. Large memory storage: Local storage of millisecond SOE event logs, fault waveform record, multi-group protection set values.
  3. Multi-protocol gateway: IEC101 serial ↔ IEC104 TCP conversion, Modbus ↔ DNP3 cross-protocol forwarding.
  4. Rack hot swap: Live replacement without rack power-off, online program download and diagnosis.
  5. Full-channel fault upload: I/O open/short fault indicated by local LED and remote SCADA alarm.


IV. Working Principle


DC24V rack power supplied to EME via backplane;Downlink: Poll DI/AI modules to collect field analog & status data, CPU executes interlock and over-limit alarm logic;Uplink: Data encapsulated by DNP3/IEC104, transmitted to SCADA via 10BASE-T Ethernet or serial port;Remote control downlink: Dispatch command parsed by EME, sent to DO boards over backplane to drive field breakers.


V. Application


  • Old 10M wired network reconstruction of 10kV/35kV distribution substation D20 RTU;
  • Thermal/Hydropower auxiliary cabinet monitoring, plant service power control;
  • Petrochemical plant substation SIS auxiliary monitoring & UPS renovation;
  • Spare replacement for in-service early D20 EME with native 10BASE-T interface.

contact us