IS200TSVOH1BDC Thermoresistor Analogue Output Board

IS200TSVOH1BDC Thermoresistor Analogue Output Board

Brand: GE

Product ID: IS200TSVOH1BDC

Condition: New / used

Terms of payment: Paypal、T/T 、Western Union

Category:

Description

1. Product Overview

IS200TSVOH1BDC is a Thermocouple & RTD Signal Output Board (TSVO) of the IS200 series for GE Vernova (formerly GE) Speedtronic Mark VI turbine control system. It is a dedicated temperature‑signal conditioning output board for gas / steam turbine TCS (Turbine Control System).


Used together with Mark VI VME control cabinets, it is widely applied in control systems for gas turbines, steam turbines, generator sets and centrifugal compressors. Receives temperature‑related digital data from the main controller, converts and outputs analog signals compatible with thermocouples and RTDs. It supports temperature‑loop simulation, signal reproduction and backup temperature transmitter output for bearing temperature, winding temperature, casing temperature and other measuring‑point signals. It serves as key hardware for temperature‑signal simulation and auxiliary transmitter output within Mark VI turbine control system.


As a standard VME backplane plug‑in board, it has passed reliability tests including high‑temperature aging, vibration‑shock and EMC electromagnetic compatibility. It enables 7×24‑hour continuous stable operation in heavy‑EMI control cabinets of power plants and petrochemical facilities. It is commonly used for spare‑part replacement, on‑site maintenance, system simulation‑commissioning and technical‑retrofit projects of gas‑steam turbine control systems.


2. Functional Features

2.1 Multi‑Channel Analog Temperature Signal Output

Receives digital temperature data from Mark VI main controller, converts data into thermocouple mV signals and RTD equivalent resistance signals with independent multi‑channel output for temperature‑signal simulation and transmitter output.


2.2 Galvanic Isolation & Signal Protection

Built‑in signal isolation and conversion circuits provide galvanic isolation between VME main‑control side and field temperature loops. It suppresses common‑mode interference and surge voltage, protects VME backplane and main‑control CPU module, and prevents reverse impact on control system from abnormal field signals.


2.3 Precision Temperature‑Signal Conditioning

High‑precision signal‑conditioning circuits are integrated. It supports conversion for multiple thermocouple calibrations (K, J, T, S, etc.) as well as Pt100 / Cu50 RTD signals to guarantee output accuracy of temperature signals.


2.4 Hardware Self‑Test and Fault Diagnosis

On‑board self‑diagnosis circuits continuously monitor board power supply, channel open‑circuit status, signal out‑of‑range conditions and board hardware faults. Once anomalies are detected, fault alarms are triggered and pop‑up alerts are generated on upper‑level HMI.


2.5 High‑Speed VME Bus Communication

Bidirectional high‑speed communication with Mark VI main‑control CPU via VME backplane bus. It receives temperature set‑point data from main controller and uploads channel diagnostic and status information of the board.


2.6 Standard VME Slot Mounting

Directly plugs into VME backplane slots inside Mark VI cabinets with locking‑latch structure for easy installation and removal. Uniform cabinet architecture for IS200‑series boards simplifies spare‑part replacement.


2.7 Harsh‑Industrial‑Environment Adaptability

Wide‑temperature operation, anti‑vibration, anti‑shock and high electromagnetic‑interference immunity. It adapts to power‑plant cabinet conditions including high temperature, dust and electromagnetic interference induced by high‑power frequency converters and motors.

IS200TSVOH2B .jpg

3. Technical Specifications

3.1 Core Compatibility Parameters

ItemSpecification
ModelIS200TSVOH1BDC
BrandGE Vernova (Formerly GE)
Product SeriesIS200 Series, Mark VI Turbine Control System
Board TypeTemperature Signal Output Board (TSVO)
Compatible SystemGE Speedtronic Mark VI TCS Turbine Control System
Mounting MethodVME backplane slot mounting
Core InterfacesAnalog temperature output terminals, VME backplane bus interface, board status LED indicators
Core FunctionsThermocouple / RTD temperature‑signal output, signal isolation & conditioning, hardware self‑diagnosis, VME‑bus data transmission
Typical ApplicationsMark‑VI‑based control systems for gas turbines, steam turbines, generator sets and compressors; temperature‑signal simulation & commissioning, bearing / casing temperature transmitter output


3.2 Electrical Performance Parameters

ItemSpecification
Output SignalThermocouple mV voltage signal, RTD equivalent resistance signal
Signal ProcessingVME‑bus command parsing, digital‑to‑temperature analog conversion, signal conditioning, galvanic isolation
Bus InterfaceVMEbus industrial bus
Power SupplyPower supplied via VME backplane
Diagnostic FunctionsChannel open‑circuit detection, output signal out‑of‑range alarm, on‑board power‑supply self‑test, LED status indication, fault upload to system
EMC PerformanceComplies with power‑plant industrial EMC standards; immunity against interference from high‑power motors and frequency converters


3.3 Environmental and Physical Parameters

ItemSpecification
Operating TemperatureWide‑temperature range for industrial cabinet deployment
Storage TemperatureWide‑temperature tolerance for spare‑part storage and transportation
Operating Humidity5 % ~ 95 % RH, non‑condensing
Environmental ResistanceVibration‑resistant, shock‑resistant, electromagnetic shielding protection; suitable for power‑plant cabinet operating conditions
Mechanical ConstructionStandard VME board, metal‑reinforced front panel, board locking latches


4. Hardware Configuration & Structural Advantages

4.1 Core Hardware Configuration

IS200TSVOH1BDC consists of VME‑bus interface circuit, data‑parsing unit, D/A conversion module, thermocouple/RTD signal‑conditioning unit, isolation‑conversion loop, on‑board power‑conversion unit, self‑diagnosis monitoring circuit, front‑panel status LED indicators, VME gold‑finger interface and metal‑reinforced front panel.

The Mark VI main controller transmits target temperature values over the VME bus. The on‑board data‑parsing unit receives digital signals, which go through D/A conversion and dedicated temperature‑conditioning circuits to output corresponding thermocouple millivolt signals or RTD equivalent resistance signals. Isolation loops isolate main‑control side from external loops. Self‑diagnosis circuits continuously monitor board power supply and output‑channel anomalies and activate front‑panel alarm LEDs upon faults. VME gold‑fingers realize backplane communication and power intake. The metal front panel enhances anti‑shock protection.


4.2 Structural & Engineering Advantages

The standard VME form factor supports plug‑in installation. Spare‑part replacement requires no extensive modification of external wiring and shortens maintenance downtime. Signal‑isolation design prevents interference from external temperature loops from coupling into VME main‑control system and protects backplane and CPU.

Multiple temperature‑signal output channels are integrated onto one single board for high integration and reduced cabinet‑space occupation. Hardware‑level self‑diagnosis enables real‑time monitoring of channel output status and rapid faulty‑channel localization to shorten on‑site troubleshooting time. Fully compatible with the IS200 hardware ecosystem of Mark VI systems, it benefits from a mature spare‑part supply chain and is widely adopted for maintenance, simulation‑commissioning and upgrade‑retrofit projects of existing gas‑ and steam‑turbine power plants.


5. Working Principle

Working sequence of IS200TSVOH1BDC: Mark VI main‑controller temperature set‑point data → VME bus → on‑board data‑parsing unit → D/A conversion + temperature‑signal conditioning → isolation loop → thermocouple / RTD analog temperature‑signal output; board diagnostic status signals → VME bus → Mark VI main‑control CPU; hardware self‑diagnosis runs in parallel.


Under unit commissioning or simulation conditions, the Mark VI main controller sends digital target‑temperature values to this board. The board converts digital values into corresponding analog temperature signals and outputs via terminals. It can be used for calibrating temperature‑acquisition boards and simulating measuring points such as bearing temperature to complete system tests.

It can also serve as auxiliary temperature‑transmitter output under normal online operating conditions to reproduce unit temperature parameters for external systems.


On‑board self‑diagnosis circuits uninterruptedly monitor power‑supply status, output‑channel open‑circuit conditions and signal out‑of‑range status. When faults are detected, front‑panel LEDs activate alarms and fault information is uploaded to DCS/HMI to notify maintenance staff, preventing system misjudgment caused by abnormal temperature‑simulation / transmitter output.


6. Common Faults and Troubleshooting

6.1 Fault LED illuminated after power‑on; system reports board fault

Possible CauseTroubleshooting MethodRemedial Action
Poor contact of VME backplane slot; oxidized gold‑fingersPower off and extract the board; inspect VME gold‑fingers for oxidation and contaminationClean gold‑fingers with lint‑free cloth; retry in an alternative VME slot
Abnormal backplane power supply; missing / under‑rated supply voltageMeasure supply voltage at VME slot terminals; inspect cabinet power modulesTroubleshoot cabinet power faults and restore backplane power supply
Damage to on‑board power‑conversion circuitBackplane power is normal while faults persist across different slotsReplace with spare IS200TSVOH1BDC board


6.2 Board communication interruption; CPU cannot send temperature set‑points or read board status

Possible CauseTroubleshooting MethodRemedial Action
VME backplane failure; damaged backplane pinsInspect backplane pins for bending and corrosion; test communication of other boards in the same slotRepair or replace VME backplane
Failure of board VME communication chipBackplane confirmed normal via cross‑slot test; this board loses communicationReplace IS200TSVOH1BDC board
Lost board configuration parameters; configuration mismatchVerify board hardware configuration inside Mark VI control softwareRe‑download board hardware configuration parameters


6.3 Main controller sends temperature set‑points, but output temperature signal has large deviation or no output

Possible CauseTroubleshooting MethodRemedial Action
Loose wiring of external output terminals; oxidized terminalsPower off and inspect wiring terminals between external loops and board output terminalsRemove terminal oxidation and retighten connections
Incorrect configuration for channel thermocouple calibration / sensor typeVerify thermocouple or RTD type settings within Mark VI configurationCorrect channel calibration parameters and download configuration
Damage to board D/A or temperature‑conditioning channelSwitch set‑points to other healthy channels and compare output resultsReplace IS200TSVOH1BDC board


6.4 Persistent channel open‑circuit fault alarm reported by system with intact external wiring

Possible CauseTroubleshooting MethodRemedial Action
Damage to board output‑conditioning loop componentsSwitch signals to other healthy channels and compare fault statusReplace IS200TSVOH1BDC board
Incorrect board‑channel range and signal‑type configurationCheck channel parameters and output‑type setup inside Mark VI configuration softwareCorrect board‑configuration parameters, download configuration and restart controller


contact us