ZM‑32‑PKZ2 is a 32A thermal-magnetic trip module for PKZ2 series motor protection circuit breakers; HI11S‑PKZ2 is the matching auxiliary contact module with one normally open and one normally closed contact. The combined assembly provides overload, short-circuit and phase-loss protection as well as status signal output for three-phase motors, widely applied in motor feeder circuits of control cabinets and MCC systems.
I. ZM‑32‑PKZ2 (Thermal-Magnetic Trip Module)
1. Basic Information
Model: ZM‑32‑PKZ2Brand: ABB (formerly Moeller)Compatible base unit: PKZ2 series motor protection circuit breakers (e.g. PKZ2‑32)Rated current range: 24~32A (adjustable via front dial)Protection functions: Thermal overload protection + magnetic short-circuit protection + sensitive phase-failure protectionMounting: Tool-free snap-on installation onto PKZ2 base frameWeight: Approx. 200g
2. Technical Specifications
Overload protection (thermal trip): Bimetallic element, Class 10 inverse time characteristic; adjustable setting Ir = 24~32AShort-circuit protection (magnetic trip): Electromagnetic instantaneous trip; pickup range: 8.5~14×Ir (approx. 275~425A)Phase-loss protection: Three-phase sensitive design for accelerated tripping upon single-phase lossRated insulation voltage Ui: 690V ACRated impulse withstand voltage Uimp: 6000VShort-circuit breaking capacity: 42kA @600V AC; 65kA @480V ACOperating temperature: -20℃~+60℃Protection class: IP20 (indoor cabinet mounting)
3. Structure & Operating Principle
Modular independent trip unit consisting of thermal elements, magnetic trip coil, mechanical latch and trip indication window.
- Overload condition: Current exceeds Ir → bimetallic strip deforms thermally → breaker trips
- Short-circuit / locked rotor condition: Heavy fault current energizes magnetic coil → instantaneous latch release & tripping (millisecond level)
- Phase loss condition: Unbalanced three-phase current creates uneven temperature across thermal elements → accelerated trip actionFront-mounted trip indicator window enables direct visual fault identification.
II. HI11S‑PKZ2 (Auxiliary Contact Module)
1. Basic Information
Model: HI11S‑PKZ2Configuration: 1NO + 1NC auxiliary contacts (1 normally open + 1 normally closed)Compatibility: PKZ2 base breaker + ZM trip blockApplication: Equipment status indication, fault alarming, interlock control and PLC signal feedbackMounting: Tool-free snap-fit installation on the right side of ZM trip module
2. Contact Ratings
Contact arrangement: 1NO + 1NCRated operational current (AC‑15): 3A @230V; 1A @400VMechanical endurance: ≥100,000 operating cyclesElectrical endurance: ≥10,000 operating cycles under rated loadProtection rating: IP20

III. Overall Features of Combination Set
- Three-in-one protection plus signal output: Overload/short-circuit/phase-loss protection together with 1NO/1NC status feedback
- High breaking capacity: Up to 65kA at 480V, eliminating requirement for upstream backup fuses
- Convenient field maintenance: Pluggable modular design for direct replacement without disconnecting main power circuit
- Wide current coverage: 24~32A rating matches 11~15kW three-phase motors at 400V system
- Robust industrial construction: Vibration-resistant, wide-temperature tolerant and high-insulation design for pumps, fans and conveyors
IV. Typical Applications
- Standalone protection & control for 11~15kW /400V three-phase asynchronous motors
- Motor feeder circuits inside control cabinets and MCC panels
- Drop-in replacement for conventional “circuit breaker + thermal overload relay” assemblies for simplified layout
- Sites requiring remote alarm, interlock logic and PLC digital feedback
V. Selection & Installation Guidelines
- Must be assembled with PKZ2‑32 base breaker; cannot work independently
- Current setting: Dial set to 1.0~1.15 × motor rated current
- Mounting sequence: Install ZM‑32‑PKZ2 first, then snap HI11S‑PKZ2 into position until audible locking click is heard
- Main circuit wiring: AWG14~AWG6 copper conductors, tightening torque:1.8N·m; only 75℃ rated copper cable permitted
- Auxiliary wiring: NO/NC terminals connect to indicator lamps, buzzers or PLC digital input modules
VI. Cross Reference of Common Series Models
ZM‑0.6‑PKZ2: 0.4~0.6AZM‑1.6‑PKZ2: 1~1.6AZM‑10‑PKZ2: 2.5~10AZM‑25‑PKZ2: 6~25AZM‑32‑PKZ2: 24~32A (this item)ZM‑40‑PKZ2: 0.6~40A