ABB REF601 CE446BB1NH Special Feeder Protection and Control Relays

ABB REF601 CE446BB1NH Special Feeder Protection and Control Relays

Brand: ABB

Product ID: REF601 CE446BB1NH

Condition: New / used

Terms of payment: Paypal、T/T 、Western Union

Category:

Description

ABB REF601 CE446BB1NH

1. Basic Information


ABB REF601 CE446BB1NH is a digital intelligent feeder protection and measurement device of ABB Relion 600 series. Designed for medium and low-voltage distribution networks, plant power circuits and industrial and mining power distribution systems, it integrates relay protection, electrical measurement, logic control, fault recording and remote communication. As the core secondary equipment for distribution automation, this high-end version of REF601 features complete hardware configuration and full functional coverage, meeting comprehensive protection and measurement requirements for conventional feeders, section switches, capacitors and small transformers.


Complying with international IEC 60255 and IEC 61000 standards, the device supports high-precision measurement, complete three-stage overcurrent protection, ground fault protection, overload protection and arc flash linkage protection. With excellent anti-electromagnetic interference performance, it adapts to 24/7 uninterrupted operation of substations, factory distribution rooms and municipal power distribution projects. It supports multi-protocol remote communication and can be seamlessly connected to SCADA and DCS power monitoring systems, widely used in new distribution automation projects, old relay protection device replacement and distribution network intelligent upgrading.


2. Technical Specifications


2.1 Core Protection Functions

  • Three-stage Overcurrent Protection: Including instantaneous overcurrent, definite-time overcurrent and overload delayed protection, which can cut off faulty circuits hierarchically for short-circuit and overload faults of distribution lines
  • Ground Fault Protection: Supports low-current ground and zero-sequence ground fault detection and tripping, adapting to single-phase ground fault protection of medium and low-voltage distribution systems
  • Auxiliary Protection: Integrated arc flash protection, over-temperature protection, frequency abnormality protection and voltage abnormality lockout protection to fully protect power distribution equipment
  • Protection Accuracy: Current measurement accuracy class 0.5, protection setting error <±5%, action time error ≤±50ms with accurate and reliable protection action
  • Fault Recording: Built-in fault recording, event logging and alarm storage functions to completely retain fault time-series data for fault tracing and maintenance analysis


2.2 Electrical I/O Specifications

  • Current Input: Software adaptive switching of 1A/5A, compatible with secondary signals of conventional current transformers with low input impedance and stable signal acquisition
  • Voltage Input: Adapts to conventional AC voltage sampling of distribution systems, accurately collecting bus and line operating voltage parameters
  • Binary Input: 4-channel programmable binary inputs for isolating switch status, switch state and external alarm signals
  • Binary Output: 6-channel programmable relay outputs for multi-channel logic control such as tripping, closing and alarming


2.3 Power Supply Specifications

  • Universal Power Range: 24~265V AC/DC wide-range universal power supply, compatible with dual AC/DC power supply modes and various distribution panel power systems
  • Voltage Tolerance: AC 85%~110% rated voltage, DC 70%~120% rated voltage, adapting to on-site voltage fluctuation conditions
  • Power Protection: Built-in overvoltage, overcurrent, surge and reverse polarity protection to resist instantaneous grid impact and wiring errors
  • Power Consumption: Low-power design with stable power consumption during long-term standby and full-load operation, low heat generation and no aging failure


2.4 Communication & Data Specifications

  • Communication Interface: Standard isolated RS485 communication port with electrical isolation design to eliminate communication crosstalk and ensure data transmission safety
  • Supported Protocols: Native compatibility with Modbus RTU and IEC 60870-5-103 power-dedicated protocols, adapting to mainstream power monitoring systems
  • Data Functions: Real-time uploading of operating parameters such as current, voltage, power, frequency and equipment status, and remote downloading of setting values and control commands
  • Data Storage: Mass storage of event records, fault waveforms and setting parameters with power-off protection for convenient operation and maintenance tracing

REF601 CE446BB1NH.jpg

2.5 Environmental & Physical Specifications

  • Operating Temperature: -25℃~+55℃ wide industrial temperature range, adapting to high and low temperature alternating conditions of outdoor and indoor distribution cabinets
  • Storage Temperature: -40℃~+85℃ with excellent temperature shock resistance for stable storage and transportation
  • Humidity Range: 5%~95%RH (non-condensing), dust-proof and moisture-proof for humid and dusty power distribution sites
  • EMC Performance: Fully compliant with IEC 61000-4 series EMC standards, strong resistance to high-voltage electromagnetic interference, frequency conversion interference and static radiation
  • Installation Mode: Standard panel embedded installation, suitable for conventional switchgear openings with stable installation and neat wiring
  • Dimensions & Weight: 130mm×160mm×151.5mm, approx. 1.43kg, compact design saving cabinet space


3. Working Principle


  1. Power-on Initialization & Self-test: After power-on, the device automatically conducts full-dimensional self-inspection of hardware circuits, sampling chips, communication ports and storage units, loads preset protection settings and control logic, and enters normal monitoring operation after passing self-test.
  2. Real-time Electrical Parameter Acquisition & Monitoring: Continuously collects core electrical parameters such as line three-phase current, bus voltage and frequency. High-precision sampling chips complete signal filtering, calibration and conversion to monitor line operating conditions in real time and capture tiny parameter fluctuations.
  3. Fault Logic Judgment & Protection Action: Built-in power protection algorithms compare real-time operating parameters with preset setting values to accurately identify faults such as short circuit, overload, ground fault and voltage abnormality. When faults occur, instantaneous or delayed tripping commands are output according to hierarchical protection logic to quickly cut off faulty circuits and isolate fault points.
  4. Status Signal Acquisition & Logic Interlock: Collects on-site switch, isolating switch and external equipment status signals through binary input ports, and completes electrical interlock, alarm prompt and status lockout combined with internal logic to avoid misoperation and equipment linkage faults.
  5. Data Recording & Fault Wave Recording: Records real-time operating data and operation events during normal operation; automatically starts wave recording at the moment of fault, completely recording pre-fault and post-fault waveforms, parameter time series and action information to support fault analysis and setting optimization.
  6. Remote Communication & Operation Maintenance: Establishes communication with upper SCADA and DCS systems through RS485 bus, uploads operating data, fault alarms and equipment status in real time, and receives remote setting modification, switching control and parameter query commands to realize unattended intelligent operation and maintenance.


4. Application Scenarios


4.1 Medium & Low Voltage Distribution Network Feeder Protection

Widely used in 10kV and below medium and low-voltage distribution lines and outgoing feeder circuits, undertaking core tasks of fault protection, cutting-off and full-condition parameter monitoring. It serves as the basic core equipment of distribution automation systems to ensure stable operation of distribution lines.


4.2 Industrial & Mining Plant Power Systems

Adapts to factory distribution rooms, workshop power cabinets and self-provided power station distribution systems, providing comprehensive protection and measurement for production power circuits, lighting circuits and auxiliary electrical equipment. It avoids production shutdown, equipment damage and safety accidents caused by electrical faults, suitable for industrial continuous production conditions.


4.3 Small Transformer & Capacitor Protection

Used as dedicated protection devices for small distribution transformers and shunt capacitor banks, accurately monitoring equipment operating status and quickly cutting off overload, short circuit and ground faults. It protects primary power distribution equipment and improves operational safety and service life.


4.4 Substation Integrated Automation System

Seamlessly connects to substation SCADA monitoring systems to realize unattended monitoring, remote control and automatic fault alarm of distribution circuits. It meets the intelligent transformation needs of small and medium-sized substations, switching stations and ring main units, improving the automation level of power distribution systems.


4.5 Compatible Replacement & Upgrade of Old Protection Devices

Perfectly replaces traditional electromagnetic relays and old microcomputer protection devices, solving common problems such as low protection accuracy, no data recording, unavailable remote communication and high failure rate of old equipment. It completes intelligent and high-precision upgrading of power distribution systems at low cost without major modification of cabinet wiring.

contact us